Sign In | Join Free | My fazendomedia.com |
|
Brand Name : Suntech
Model Number : SCO12
Certification : ISO
Place of Origin : China
MOQ : 1 Set
Price : Get the newest price
Payment Terms : L/C, T/T, Western Union
Supply Ability : 30000PCS Per Month
Delivery Time : 7-10 days after deposit
Packaging Details : Box with Pattets For Shipping
Product Name : electric fuse cutout
Safety Standards : IEC
OEM : Available
Rated Voltage : 10KV
Material : Silicone rubber
Rated Current : 100A
Voltage Outdoor High Quality 12kv Polymer Expulsion Fuse Cutout
Overview:
Drop out fuses and load-drop fuses are outdoor high voltage protection appliances. It is installed on the high voltage side of the distribution transformer or on the branch line of the distribution line. used as a short circuit of the transformer and the line, overload protection and split load current.
Advantage:
1. Small size,Light weight,resistance to impact,no collision damage during transportation,flexible installation,suitable for use in the switch cabin.
2. Special structure,the overall compression molding,no air gap,good sealing performance,moisture-proof and explosion-proof 3. Large creepage distance,good hydrophobicity,strong stain resistance,stable performance and reduce operation maintenance. 4. Unique formula of zinc oxide varistor, small leakage current,slow aging,long service life.
5. With DC reference voltage,rectangular flow capacity and high current and large current withstand capacity are higher than standard requirement.
porcelain drop out fuse product parameters | ||||||||
Type | Rated voltage (KV) |
Rated current (A) |
Breaking current (A) |
Lightning Impulse voltage(BIL) |
Power frequency wihstand voltage |
Creepage distance |
Weight (kg) |
Dimensions (cm) |
STP3-24/100 | 24-27 | 100 | 10000 | 150 | 65 | 540 | 11 | 51×38×16 |
STP3-24/200 | 24-27 | 200 | 12000 | 150 | 65 | 540 | 11.5 | 51×38×16 |
STP3-24/100F | 24-27 | 100 | 10000 | 150 | 65 | 540 | 11.5 | 51×38×16 |
STP3-24/200F | 24-27 | 200 | 12000 | 150 | 65 | 540 | 12 | 51×38×16 |
STP4-33/100 | 33-36 | 100 | 10000 | 170 | 72 | 680 | 12 | 60×41×14 |
STP4-33/200 | 33-36 | 200 | 12000 | 170 | 72 | 680 | 12.5 | 60×41×14 |
STP4-33/100F | 33-36 | 100 | 10000 | 170 | 72 | 680 | 12 | 60×41×14 |
STP4-33/200F | 33-36 | 200 | 12000 | 170 | 72 | 680 | 12.5 | 60×41×14 |
Composite drop out fuse product parameters | ||||||||
Type | Rated voltage (KV) |
Rated current (A) |
Breaking current (A) |
Lightning Impulse voltage (BIL)(KV) |
Power frequency wihstand voltage |
Creepage distance |
Weight (kg) |
Dimensions (cm) |
STC1-12/100 | 11-15 | 100 | 8000 | 110 | 42 | 370 | 4.5 | 41×35×12 |
STC1-12/200 | 11-15 | 200 | 10000 | 110 | 42 | 370 | 5 | 41×35×12 |
STC2-12/100 | 11-15 | 100 | 10000 | 110 | 55 | 530 | 5 | 51*38*11 |
STC2-12/200 | 11-15 | 200 | 12000 | 110 | 55 | 530 | 5.3 | 51*38*11 |
STC3-24/100 | 24-27 | 100 | 10000 | 150 | 65 | 720 | 5.3 | 53×35×11 |
STP3-24/200 | 24-27 | 200 | 12000 | 150 | 65 | 720 | 5.6 | 53×35×11 |
STC4-33/100 | 33-36 | 100 | 10000 | 170 | 72 | 970 | 6.8 | 87×45×14 |
STC4-33/200 | 33-36 | 200 | 12000 | 170 | 72 | 970 | 7.3 | 87×45×14 |
![]() |
100A 12kv Polymer Expulsion Fuse Cutout Light Weight Images |